High Colonic Equipment

 


High Colonic Equipment

Angel of Water® US Distributors | (800) 834-9945 or (908) 451-5748 | jim@cleansinginstitute.com

 

 

Description of Valves Each of the valves on the Angel of Water® CM-1 Surround is named and numbered. The valves and their functions are easy to learn and can be mastered in a short period of time. Their descriptions are as follows:

Valves #1 and #2 are accessed through the small side door located on the tower cabinet:

#1 Tank Fill – when open, allows water into tank

#2 Tank Drain – when open, empties tank Valves #3 - #8 are accessed through the back folding door located on the tower cabinet:

#3 Tank Maintenance Exit – when open, used for maintenance and disinfection protocols

#4 Maintenance Flow – when open, allows water to flow through nylon nipple for maintenance and disinfection protocols

#5 Recirculating Tank Maintenance Exit – when open, allows water to exit recirculating tank for maintenance and trouble-shooting protocols

#6 UV Inlet/Patient Flow – when open, allows water into UV Filter and then to the patient. When partially closed, slows flow to patient. When fully open, allows full flow to patient

#7 Recirculating Tank Bypass – when open, keeps water from entering small tank when Valve #8 is closed. Used for Valve Sequence B of Regular Operation Mode as explained on p. 33

#8 Recirculating Tank Inlet – when open, allows water into small tank Valves

#9 and #10 are accessed through the large door located on the basin cabinet:

#9 Cold Inlet – when open, allows cold water source into System

#10 Hot Inlet – when open, allows hot water source into System

The following three valves are located on the fiberglass basin topside:

Volume Control Valve for Personal Sprayer (left side) - adjusts sprayer water volume for personal hygiene and for rinsing basin

Viewing Tube Flush Valve (right side) - flushes waste matter through viewing tube line and down drain

Water Mixing Valve (right side) - mixes hot and cold water for tank fill and personal sprayer use

The following valve is located inside main tank:

Tank Level Valve - automatically shuts off water fill into large main tank

The following valve is the only electrical valve on the System and is located on the middle shelf of the tower cabinet. It is accessed through the tower bifold doors.

Solenoid Valve - activated by FLOW switch(es) on control panel(s)

The following two valves are permanent plumbing safety features:

Basin Backflow Prevention (Ball Check) Valve - prevents water from flowing back into the line once it has passed from the basin nipple to the nozzle and into the person’s rectum This valve is located underneath the basin and is connected directly to the basin nipple through the basin wall.

Viewing Tube Sprayer Backflow Prevention (Spring-loaded) Valve – prevents water that is flushed into viewing tube from backing into clean water line This valve is located directly inside the basin cabinet large doors. It is reachable on the upper right of the door opening.

 

Valve Sequences for System operation
The mode of operation for the Angel of Water® CM-1 Surround is called regular operation Mode. All colon hydrotherapy sessions are to be conducted in regular operation Mode Sequence A. The System is shipped with valves preset for Regular Operation Mode Sequence A. Double check that the valves are opened and closed as described below before beginning your first session.

 

Regular Operation Mode (used for all colon hydrotherapy sessions)

Regular Operation features water circulating from the main tank via the water cycling device to the recirculating tank. An even and constant stream of gravity-fed water then flows through the UV Filter to the patient at approximately 1 p.s.i.. (NOTE: Municipal water supplies generally flow at a rate of 60 or more p.s.i..)

Valve Sequence A:
Open Valves #6 and #8 (#9 and #10 were set in OPEN position when System was set up and should be left
OPEN always unless System plumbing maintenance requires otherwise). Valves #3, #4, #5, and #7 are closed.
Then open Valve #1 and turn on and adjust Water Mixing Valve to fill tank with water between 99 to 103 degrees
Fahrenheit (approximately 37 - 39 C.).
Close Valve #1 OR shut off Water Mixing Valve to stop water to main tank at any level. However, water level
inside main tank shuts off automatically by Tank Level Valve once level has reached top (about 8 gallons or 32 L).
Once full, close #1 and/or turn off Water Mixing Valve. As water is needed in tank, open #1 and/or turn
on Water Mixing Valve to refill tank during session to prevent fluctuations in water temperature.

 

Valve Sequence B:
Occasionally, the patient may feel as if no water is coming into the colon. This may indicate that the nozzle is clogged at the tip with waste material. The healthcare practitioner can facilitate unclogging the nozzle without having the patient come off the nozzle. To unclog nozzle with additional flow from large main tank, close
Valve #8. Then gradually open Valve #7 until flow is felt again by patient. Once person feels water flowing, close Valve #7 completely and fully open Valve #8.

In the unlikely event of a power outage to the System, have the patient slide off the rectal nozzle and stop the session. You may resume session once the power to the System has been restored.

Maintenance Sequence:
This sequence involves the opening of Valves #3, #4, and #5 and the closing of Valve #6 during the tank disinfection protocol fully explained on p. 34.

 

WATCH DEMO

Medical Opinions | BUY NOW | Installation | Starting a Colon Therapy Business | Pictures | Accessories/Supplies | User Manual | Training/ Certification

Conducting a Session | Routine Maintenance | Cleaning Unit | Trouble Shooting | Features | Control Panel Switches | Valve Settings

SAMPLE FLOOR PLAN | DESIGNING YOUR ROOM | BLANK FLOOR PLAN | ARIAL VIEW

 

Angel of Water® US Distributors | 6 Crestwood Road, Gillette NJ 07933 | (800) 834-9945 or (908) 451-5748 | Fax (908) 598-7449 | jim@cleansinginstitute.com

BACK TO HOME PAGE